booster set controller

For 5–10 floors, booster sets, PM821-16 is the right choice: pump current 8 – 16 A, pump power up to 3 kW.

Who is this page for?

For 5–10 floors, booster sets, PM821-16 is the right choice: pump current 8 – 16 A, pump power up to 3 kW.

Model selection guide

Model selection table
Pump currentPump powerModelTypical use
up to 8 Aup to 1.5 kWPM821-81–4 floors, homes and shops
8 – 16 Aup to 3 kWPM821-165–10 floors, booster sets
up to 25 Aup to 4 hpPM821-25Residential, commercial and agricultural

The current on the pump nameplate decides the model, nothing else.

How it works

  1. The pressure sensor measures the line pressure continuously.
  2. When the pressure falls to the F2 value, the unit soft-starts the pump.
  3. When the pressure reaches the F1 value, the unit soft-stops the pump.
  4. If the pump current rises above F3, or no water arrives, the unit stops the pump and shows a fault code.

Technical specifications

Technical specifications
PropertyPM821-8PM821-16Unit
Maximum pump current816A
Maximum pump power1.53kW
Peak starting current1030A
Supplied sensor pressure range0 – 200 – 20bar
Pressure sensor threadG1/4G1/4female
Input voltage180 – 240180 – 240V
Output voltageequal to input
Unit's own consumption< 5< 5W
Operating temperature-15 – 55-15 – 55°C
Weight, boxed650650g

These figures come from the HYDROSET PM821 user manual (hardware A3.3, software 4.0). The manual covers PM821-8 and PM821-16 only, so no column is shown for PM821-25.

Price and ordering

The price of PM821-8 and PM821-16 is on each product page. PM821-25 is made to order and has no published price; contact the company for it.

PM821-16Product page

Frequently asked questions

Recommended model

For 5–10 floors, booster sets, PM821-16 is the right choice: pump current 8 – 16 A, pump power up to 3 kW.

What if the pump nameplate current is unreadable?

Tell the company the number of floors and units and a model will be suggested. The model selection guide also carries a floors-to-model table.

What happens if the pump is stronger than the model's rating?

The unit raises fault E1 (over current) and stops the pump. Always pick a model rated at or above the pump's nameplate current.

Last updated:

booster set controller | model choice | price | KFGTECH